Transformer Testing
GD200-40WA Dual-Channel DC Winding Resistance Tester
Dual constant-current-source DC winding resistance tester with separate high-voltage and low-voltage channels, designed for temperature-rise tests on transformers up to 35kV where HV and LV winding resistances differ greatly.

Overview
Dual constant-current-source DC winding resistance tester with separate high-voltage and low-voltage channels, designed for temperature-rise tests on transformers up to 35kV where HV and LV winding resistances differ greatly.
Standards & Compliance
Benchmark standards for this equipment category
Systems in this category are commonly specified against these standards, linked to the issuing body. Final configuration and acceptance criteria follow the standard and edition you nominate.
- IEC 60076-1 — Power transformers - General
- IEC 60076-3 — Insulation levels and dielectric tests
- IEC 60076-5 — Ability to withstand short circuit
- IEEE C57.12.90 — Test code for liquid-immersed distribution and power transformers
- GB 1094 — Power transformers
- GB 50150 — Hand-over test of electrical equipment
Application Scenarios
Request Specifications & Quotation
Tell us your test object ratings, the test items you need and the applicable standards. Our sales engineers reply with a configuration proposal and a formal quotation within 24 hours.
Get a QuoteDetailed Description
Overview: DC winding resistance is a mandatory test for transformers during manufacturing, factory testing, installation, handover and preventive testing. It detects material, welding, loose-connection, missing-strand and broken-wire defects and hidden dangers after operation.
Design: the instrument uses dual constant-current-source design, CPU-controlled charge/discharge sequencing and complete protection, so it is very suitable for temperature-rise tests on transformers whose HV and LV winding resistances differ greatly. It supports simultaneous or separate HV and LV side testing.
Output and range: the maximum output current is 20 A and the maximum range is 2kΩ, suitable for temperature-rise testing and DC resistance measurement of all transformers at 35kV and below. The HV channel (CH1) provides 5A/1A/0.1A/0.01A and the LV channel (CH2) provides 20A/10A/5A/2A.
Protection and storage: the instrument features AC380V misconnection protection and alarm, wire-break anti-arc protection, and audible discharge alarm. It includes a calendar, 100 groups of conventional data storage and two temperature-rise test result stores, with a USB port for exporting data and generating temperature-rise curves.
Technical Specifications
| Output current (HV CH1) | 5A, 1A, 0.1A, 0.01A |
|---|---|
| Output current (LV CH2) | 20A, 10A, 5A, 2A |
| Range (HV CH1 - 5A) | 0Ω-4Ω |
| Range (HV CH1 - 1A) | 20mΩ-20Ω |
| Range (HV CH1 - 0.1A) | 200mΩ-200Ω |
| Range (HV CH1 - 0.01A) | 2Ω-2000Ω |
| Range (LV CH2 - 20A) | 0Ω-0.1Ω |
| Range (LV CH2 - 10A) | 2mΩ-0.4Ω |
| Range (LV CH2 - 5A) | 4mΩ-0.8Ω |
| Range (LV CH2 - 2A) | 10mΩ-2Ω |
| Accuracy (HV CH1) | 0.2%±1μΩ |
| Accuracy (LV CH2) | 0.2%±0.2μΩ |
| Minimum resolution | 0.1μΩ |
| Temperature-rise recording interval | 10s, 30s, 60s |
| Operating temperature | -20°C to 40°C |
| Humidity | ≤80%RH, no condensation |
| Power supply | AC220V±10%, 50Hz±1Hz |
| Dimensions | 410mm x 440mm x 210mm |
| Net weight | 15.7kg |
Frequently Asked Questions
What is the GD200-40WA Dual-Channel DC Winding Resistance Tester used for?
Why does it have two channels?
How do I get a quotation?
Further Reading
Method and selection guides that cover the tests this instrument performs.
Reviewed by the Application Engineering Team at Nanjing Gaodian Electric Power Equipment
Specifications are taken from the manufacturer’s technical documentation. Final configuration and acceptance criteria follow the standard and edition you nominate — tell us your test list and we will confirm the ratings.
Related Products

ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System
Automatic evaluation system for the energy-efficiency grade of distribution transformers up to 800 kVA at 10 kV/0.4 kV. Combines intelligent test sequence control, automatic wiring changeover, data processing, data upload and report generation in one bench.

GD230 Ground Continuity Tester
Portable instrument for measuring the continuity resistance between the grounding down conductors of individual items of equipment in a substation. Controlled by a high-performance MCU with automatic current selection, on-board data retention and a thermal printer.

GD-300B Transformer Short-Circuit Impedance Tester
Measures transformer short-circuit impedance, short-circuit reactance, short-circuit resistance and three-phase impedance voltage. Uses dual A/D synchronous AC sampling and DSP for winding deformation assessment in the field.

GD-300D Reactor Electrical Parameter Tester (Portable)
Portable instrument dedicated to measuring the electrical parameters of single-phase and three-phase reactors, including AC phase voltage RMS, average voltage, current RMS, active power, reactance and inductance, at 0.5 class accuracy.

DC Winding Resistance Tester
Portable instrument for DC resistance measurement of inductive equipment such as transformers, motors and instrument transformers (CT/PT). Fully software-controlled with back-EMF protection and field anti-interference capability.

GD-300D Reactor Electrical Parameter Tester (Built-in)
Panel-mounted version of the GD-300D reactor electrical parameter tester, using a 320 x 240 dot-matrix LCD with multi-screen menu operation and direct measurement of three-phase reactance, inductance and total active power.
More in Transformer Testing
- •ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System
- •GD-300B Transformer Short-Circuit Impedance Tester
- •DC Winding Resistance Tester
- •GD-400A Transformer Capacity & No-Load Loss Tester
- •GDBZ-IV Transformer Test Bench
- •GDBZ-III Transformer Comprehensive Test Bench
- •Transformer Intelligent Logistics Line Test System
- •GDBZ-IV 220/110kV Main Transformer Comprehensive Test System
- •GDBZ-IV Automatic Transformer Comprehensive Test System
- •GD700A Automatic Turns Ratio Tester
- •GDRZ Transformer Winding Deformation Tester
- •GD-810 Transformer On-Load Tap-Changer Tester
- •GD300C Power Analyzer
- •GD-700 Automatic Turns Ratio & Vector-Group Tester
Need the datasheet for this model?
Send us this product name plus your test requirements. We reply with specifications, photos and a formal quotation.