Transformer Testing

GD200-40WA Dual-Channel DC Winding Resistance Tester

Dual constant-current-source DC winding resistance tester with separate high-voltage and low-voltage channels, designed for temperature-rise tests on transformers up to 35kV where HV and LV winding resistances differ greatly.

GD200-40WA Dual-Channel DC Winding Resistance Tester

Overview

Dual constant-current-source DC winding resistance tester with separate high-voltage and low-voltage channels, designed for temperature-rise tests on transformers up to 35kV where HV and LV winding resistances differ greatly.

Standards & Compliance

Benchmark standards for this equipment category

Systems in this category are commonly specified against these standards, linked to the issuing body. Final configuration and acceptance criteria follow the standard and edition you nominate.

Application Scenarios

Transformer temperature-rise testingDC winding resistance measurementTesting transformers up to 35kVHV/LV simultaneous or separate measurement

Request Specifications & Quotation

Tell us your test object ratings, the test items you need and the applicable standards. Our sales engineers reply with a configuration proposal and a formal quotation within 24 hours.

Get a Quote

Detailed Description

Overview: DC winding resistance is a mandatory test for transformers during manufacturing, factory testing, installation, handover and preventive testing. It detects material, welding, loose-connection, missing-strand and broken-wire defects and hidden dangers after operation.

Design: the instrument uses dual constant-current-source design, CPU-controlled charge/discharge sequencing and complete protection, so it is very suitable for temperature-rise tests on transformers whose HV and LV winding resistances differ greatly. It supports simultaneous or separate HV and LV side testing.

Output and range: the maximum output current is 20 A and the maximum range is 2kΩ, suitable for temperature-rise testing and DC resistance measurement of all transformers at 35kV and below. The HV channel (CH1) provides 5A/1A/0.1A/0.01A and the LV channel (CH2) provides 20A/10A/5A/2A.

Protection and storage: the instrument features AC380V misconnection protection and alarm, wire-break anti-arc protection, and audible discharge alarm. It includes a calendar, 100 groups of conventional data storage and two temperature-rise test result stores, with a USB port for exporting data and generating temperature-rise curves.

Technical Specifications

Output current (HV CH1)5A, 1A, 0.1A, 0.01A
Output current (LV CH2)20A, 10A, 5A, 2A
Range (HV CH1 - 5A)0Ω-4Ω
Range (HV CH1 - 1A)20mΩ-20Ω
Range (HV CH1 - 0.1A)200mΩ-200Ω
Range (HV CH1 - 0.01A)2Ω-2000Ω
Range (LV CH2 - 20A)0Ω-0.1Ω
Range (LV CH2 - 10A)2mΩ-0.4Ω
Range (LV CH2 - 5A)4mΩ-0.8Ω
Range (LV CH2 - 2A)10mΩ-2Ω
Accuracy (HV CH1)0.2%±1μΩ
Accuracy (LV CH2)0.2%±0.2μΩ
Minimum resolution0.1μΩ
Temperature-rise recording interval10s, 30s, 60s
Operating temperature-20°C to 40°C
Humidity≤80%RH, no condensation
Power supplyAC220V±10%, 50Hz±1Hz
Dimensions410mm x 440mm x 210mm
Net weight15.7kg

Frequently Asked Questions

What is the GD200-40WA Dual-Channel DC Winding Resistance Tester used for?
It measures the DC resistance of transformer windings, a mandatory test for transformer manufacturing, factory, installation, handover and preventive testing. It reliably detects manufacturing defects such as material, welding, loose connections, missing strands and broken wires.
Why does it have two channels?
During temperature-rise tests on distribution transformers, the HV and LV winding resistances differ greatly and a traditional single constant-current source cannot be used. The instrument uses dual constant-current sources with CPU-controlled charge/discharge sequencing and full protection, making it ideal for temperature-rise tests where HV and LV windings differ greatly.
How do I get a quotation?
Email your transformer rating and test requirements to bowen@harchin.com. The instrument is manufactured in our Nanjing facility and quoted directly from the factory based on your configuration.

Reviewed by the Application Engineering Team at Nanjing Gaodian Electric Power Equipment

Specifications are taken from the manufacturer’s technical documentation. Final configuration and acceptance criteria follow the standard and edition you nominate — tell us your test list and we will confirm the ratings.

Related Products

ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System
Transformer Testing

ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System

Automatic evaluation system for the energy-efficiency grade of distribution transformers up to 800 kVA at 10 kV/0.4 kV. Combines intelligent test sequence control, automatic wiring changeover, data processing, data upload and report generation in one bench.

GD230 Ground Continuity Tester
Power Testing Instruments

GD230 Ground Continuity Tester

Portable instrument for measuring the continuity resistance between the grounding down conductors of individual items of equipment in a substation. Controlled by a high-performance MCU with automatic current selection, on-board data retention and a thermal printer.

GD-300B Transformer Short-Circuit Impedance Tester
Transformer Testing

GD-300B Transformer Short-Circuit Impedance Tester

Measures transformer short-circuit impedance, short-circuit reactance, short-circuit resistance and three-phase impedance voltage. Uses dual A/D synchronous AC sampling and DSP for winding deformation assessment in the field.

GD-300D Reactor Electrical Parameter Tester (Portable)
Reactor & Arc Suppression Coil Testing

GD-300D Reactor Electrical Parameter Tester (Portable)

Portable instrument dedicated to measuring the electrical parameters of single-phase and three-phase reactors, including AC phase voltage RMS, average voltage, current RMS, active power, reactance and inductance, at 0.5 class accuracy.

DC Winding Resistance Tester
Transformer Testing

DC Winding Resistance Tester

Portable instrument for DC resistance measurement of inductive equipment such as transformers, motors and instrument transformers (CT/PT). Fully software-controlled with back-EMF protection and field anti-interference capability.

GD-300D Reactor Electrical Parameter Tester (Built-in)
Reactor & Arc Suppression Coil Testing

GD-300D Reactor Electrical Parameter Tester (Built-in)

Panel-mounted version of the GD-300D reactor electrical parameter tester, using a 320 x 240 dot-matrix LCD with multi-screen menu operation and direct measurement of three-phase reactance, inductance and total active power.

Need the datasheet for this model?

Send us this product name plus your test requirements. We reply with specifications, photos and a formal quotation.