GD-210 Large Ground-Grid Resistance Tester (Type CA)

Dedicated instrument for measuring the grounding resistance of large earth grids and the continuity between grounding points. Uses variable-frequency anti-interference technology, so it needs no high-current supply and can take accurate readings even inside a strongly interfering substation environment.

GD-210 Large Ground-Grid Resistance Tester (Type CA)

Overview

Dedicated instrument for measuring the grounding resistance of large earth grids and the continuity between grounding points. Uses variable-frequency anti-interference technology, so it needs no high-current supply and can take accurate readings even inside a strongly interfering substation environment.

Standards & Compliance

Benchmark standards for this equipment category

Systems in this category are commonly specified against these standards, linked to the issuing body. Final configuration and acceptance criteria follow the standard and edition you nominate.

Application Scenarios

Large earth-grid grounding resistance measurementGrounding continuity testing between grid pointsOn-site substation measurement under strong 50 Hz interferenceSoil resistivity measurement

Request Specifications & Quotation

Tell us your test object ratings, the test items you need and the applicable standards. Our sales engineers reply with a configuration proposal and a formal quotation within 24 hours.

Get a Quote

Detailed Description

Overview: the GD-210 is a dedicated instrument for measuring the grounding resistance of earth grids and the grounding continuity between grid points. It adopts a variable-frequency AC supply and a microcomputer-controlled measurement and signal-processing scheme, which solves the anti-interference problem, simplifies the test procedure and greatly reduces labour intensity and testing cost.

Measurement capability: the instrument measures grounding impedance and grounding resistance simultaneously, giving a truer picture of the actual characteristics of the earth grid. It can also measure the current stake, the voltage stake, ground-grid impedance, grounding resistance, grounding continuity and soil resistivity.

Accuracy: the basic error is only 0.005Ω, which allows it to measure very large earth grids with very low grounding impedance. The measurement range is 0-500Ω (including current-stake impedance) with a resolution of 0.001mΩ.

Safety: the instrument is fitted with grounding protection, current-limiting and voltage-limiting protection, and audible and visual alarms to keep both the operator and the equipment safe.

Technical Specifications

Measurement range0-500Ω (including current-stake impedance)
Resolution0.001mΩ
Measurement error±(reading x 1% + 0.005Ω)
Power-frequency (50 Hz) interference withstand10V
Test current waveformSine wave
Maximum output current3A
Maximum output voltage100V
Measurement leadsCurrent lead copper cross-section ≥1.5mm²; voltage lead ≥1.0mm²
Power supplyAC220V±10%, 50Hz
Dimensions368x268x211 mm
Weight6kg

Frequently Asked Questions

What is the GD-210 Large Ground-Grid Resistance Tester used for?
It measures the grounding resistance of large earth grids and the grounding continuity between grounding points. Unlike the traditional power-frequency high-current three-pole method, it uses a variable-frequency AC source and does not need a test current of 30 A or more, so the test equipment stays light and the whole process is much simpler.
What makes it accurate in a live substation?
The instrument uses a variable-frequency (different-frequency) measurement method combined with modern hardware and software filtering. The test current waveform is a sine wave whose frequency is close to power frequency, and it withstands up to 10 V of 50 Hz voltage interference, so readings stay stable and reliable even in strong-interference environments.
How do I get a quotation?
Email your grid size, required range and site conditions to bowen@harchin.com. The instrument is manufactured in our Nanjing facility, so we quote directly from the factory. Pricing depends on configuration, so please send your specification rather than asking for a list price.

Reviewed by the Application Engineering Team at Nanjing Gaodian Electric Power Equipment

Specifications are taken from the manufacturer’s technical documentation. Final configuration and acceptance criteria follow the standard and edition you nominate — tell us your test list and we will confirm the ratings.

Related Products

GD230 Ground Continuity Tester
Power Testing Instruments

GD230 Ground Continuity Tester

Portable instrument for measuring the continuity resistance between the grounding down conductors of individual items of equipment in a substation. Controlled by a high-performance MCU with automatic current selection, on-board data retention and a thermal printer.

ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System
Transformer Testing

ECBZ-GD Energy-Efficient Transformer Energy-Grade Evaluation System

Automatic evaluation system for the energy-efficiency grade of distribution transformers up to 800 kVA at 10 kV/0.4 kV. Combines intelligent test sequence control, automatic wiring changeover, data processing, data upload and report generation in one bench.

ETCR200 Clamp-on Ground Resistance Tester
Power Testing Instruments

ETCR200 Clamp-on Ground Resistance Tester

Clamp-on ground resistance tester for power, telecom, meteorological and other electrical installations. Measures without auxiliary electrodes, so no disconnection of the grounding conductor and no electrode layout error.

GD-300D Reactor Electrical Parameter Tester (Portable)
Reactor & Arc Suppression Coil Testing

GD-300D Reactor Electrical Parameter Tester (Portable)

Portable instrument dedicated to measuring the electrical parameters of single-phase and three-phase reactors, including AC phase voltage RMS, average voltage, current RMS, active power, reactance and inductance, at 0.5 class accuracy.

GD-500 Automatic Capacitance & Inductance Tester
Power Testing Instruments

GD-500 Automatic Capacitance & Inductance Tester

Bench instrument for measuring high-voltage shunt capacitor banks of reactive power compensation installations and for reactor measurement, without disconnecting the capacitor leads. Uses four-terminal measurement and provides on-board data storage with USB transfer.

GD-300D Reactor Electrical Parameter Tester (Built-in)
Reactor & Arc Suppression Coil Testing

GD-300D Reactor Electrical Parameter Tester (Built-in)

Panel-mounted version of the GD-300D reactor electrical parameter tester, using a 320 x 240 dot-matrix LCD with multi-screen menu operation and direct measurement of three-phase reactance, inductance and total active power.

Need the datasheet for this model?

Send us this product name plus your test requirements. We reply with specifications, photos and a formal quotation.