Almost every test an HV laboratory performs is governed by one of three standards systems: IEC at international level, IEEE in North America, and in China the GB national series, the DL electric-power industry series and the JJG metrology series. An enquiry, a test procedure and an acceptance report therefore often name all three at once, because an instrument may be built to an IEC design, judged against a GB 50150 acceptance criterion, and verified under a JJG regulation — three different documents answering three different questions.
This page is a working cross-reference rather than a lecture. It sets out how the systems relate, maps test domains to the standards that actually define them, and explains what to write in an enquiry and in a test report so that the standard, its part and its edition are unambiguous. Nothing here claims that a particular instrument is certified or compliant to any standard; equipment is configured to the standard the customer specifies.
How the three systems relate
IEC and IEEE: where the border actually runs
IEC standards are produced by international technical committees and are the default reference in Europe, most of Asia, the Middle East, Africa and South America. IEEE standards are developed in the United States and dominate North American specifications, utility practice and procurement documents. The two are not translations of one another: IEC 60076 and IEEE C57.12.90 both cover power-transformer testing, but the clause structure, the terminology and parts of the test sequence differ, and a report written to one is not automatically acceptable under the other. In practice the field has converged on IEC 60060-1 as the description of how a dielectric test voltage is generated, measured and corrected for atmospheric conditions, while North American projects still cite IEEE 4 for high-voltage test techniques and IEEE C57.12.90 for the transformer test code. Where a specification cites both, the stricter requirement governs; where the test method comes from one document and the acceptance limit from the other, the report has to say so rather than silently merge the two.
GB, DL and JJG: three layers, three purposes
The Chinese system is layered by legal function, and the layers are not interchangeable. GB standards (mandatory, or recommended as GB/T) form the national level and are very often related to IEC text: a GB standard may be an identical adoption of an IEC document, an adoption with national deviations, or a genuinely national document with no IEC parent. DL standards are electric-power industry standards, written for utility engineering and maintenance work, and several field tests with no direct IEC equivalent sit there. JJG documents are metrology verification regulations; they govern whether an instrument calibration is traceable and legally valid, not whether a product passes a dielectric test. Read as a whole: GB tells you how to test and what to accept, DL tells a Chinese utility how to check equipment in service, and JJG tells a calibration laboratory how to verify the instrument. Citing DL/T 596 as if it were a type-test standard, or treating a JJG verification certificate as a product approval, is a common and avoidable error.
Cross-reference: test domain to governing standard
| Test domain | IEC | IEEE | GB / DL / JJG |
|---|---|---|---|
| Power transformers — general requirements, routine and type tests | IEC 60076-1 | IEEE C57.12.90 | GB 1094.1 |
| Power transformers — dielectric tests and insulation levels | IEC 60076-3 | IEEE C57.12.90 | GB 1094.3 |
| Power transformers — short-circuit withstand | IEC 60076-5 | IEEE C57.12.90 | GB 1094.5 |
| Power transformers — temperature rise and loading | IEC 60076-2 | IEEE C57.12.90 | GB 1094.1 (general part) |
| On-site hand-over and acceptance testing of substation equipment | — | — | GB 50150 |
| Instrument transformers (CT and PT) — general requirements | IEC 61869-1 (superseding IEC 60044-1 and IEC 60044-2) | IEEE C57.13 | GB 1208 (CT); GB 1207 (PT) |
| Instrument transformers — type and routine tests | IEC 61869-2 (CT); IEC 61869-3 (PT) | IEEE C57.13 | GB 1208 (CT); GB 1207 (PT) |
| High-voltage test techniques, measuring systems and their validation | IEC 60060-1; IEC 60060-2 | IEEE 4 | GB/T 16927.1 |
| Partial discharge measurement | IEC 60270 | — | GB 7354; DL 417 |
| Field diagnostics and condition assessment — winding deformation, loop and contact resistance, insulation resistance, earthing | — | IEEE 43 (insulation resistance); IEEE 81 (earthing) | DL/T 911 (FRA); DL/T 845 (loop and contact resistance); DL/T 596 (maintenance testing) |
Reading the table, and why editions matter
- •Start from the test item on your acceptance list rather than from a standard number. A report that cites "IEC 60076" is ambiguous, because the series is split into parts and each part covers a different test family with different criteria.
- •Put the standard number, the part number and the edition year on the procedure and repeat all three on the report. A dielectric test judged against an older edition may not satisfy a specification that names the current one, and the difference becomes invisible once the report leaves the test bay.
- •Where a GB standard is an identical adoption of an IEC document, an IEC-based test procedure can normally be used unchanged — but the acceptance criteria and the report wording should follow the GB text that the contract names.
- •Where editions differ, agree in writing before the test which one governs. The clauses that change most often are atmospheric correction, the definition of the test voltage, and the duration and sequence of applied voltages. Retro-fitting a criterion after the test is the most common cause of a rejected report.
- •Treat DL and JJG documents as what they are: DL for in-service maintenance and field diagnostics, JJG for metrological verification of the instrument. Neither substitutes for the type-test standard of the product, even when both are cited in the same acceptance file.
- •Record calibration traceability separately from test results. A measuring system is only usable if its calibration is valid on the test date and the scale factor in use matches the certificate — that is a JJG-series or equivalent verification question, not a dielectric-test question.
- •Note the equipment-safety layer too: IEC 61010 covers the safety requirements for electrical measuring and test equipment, and IEC 60085 covers insulation thermal classification. They are not test-acceptance standards, but they are frequently named in specifications for the bench itself.
Specifying a standard in a purchase enquiry
- •Name the product and the standard together: power transformers to IEC 60076-1 or GB 1094.1, instrument transformers to IEC 61869-1 or GB 1208 / GB 1207, high-voltage test techniques to IEC 60060-1 or GB/T 16927.1.
- •State whether the contract depends on a specific edition. If you accept any current edition, say so and require the supplier to declare which edition the delivered procedures follow.
- •List test items, not equipment: applied withstand, induced withstand, lightning impulse, partial discharge, temperature rise, ratio and polarity, winding resistance, turns ratio, and a baseline for frequency-response analysis.
- •Give the acceptance limits and their source — a clause number with edition, an internal specification, or the technical schedule of your own customer — so the supplier can configure the test sequence and the report template to match.
- •Say which reporting language and format you need, whether the report must be witnessed by a third party, and whether raw waveforms must be archived with the result.
- •Ask for calibration and verification documents as a separate deliverable: state which regulation governs the verification of each instrument or measuring system and how the reference is traced.
- •Where acceptance happens on site under GB 50150, state it as an on-site hand-over requirement rather than a factory type test. The two have different scopes, different evidence and, in practice, different equipment.
A cross-reference table cannot replace the standards themselves — it tells you which document to open, and it prevents the more expensive mistake of running the right method with the wrong acceptance criterion. Keep the mapping in the enquiry file, write the standard, part and edition into every test procedure before the first voltage is applied, and require the same three identifiers on the report. That is what makes a test record usable years later, in another country, by an engineer who was not in the room.
Reviewed by the Application Engineering Team at Gaodian Electric Power Co., Ltd
Gaodian Electric Power Co., Ltd designs and manufactures high-voltage test systems for transformer factories, power utilities and third-party laboratories. This guide is a selection reference, not a compliance statement: final equipment configuration and acceptance criteria follow the standard and edition you nominate.






